Measurement of the harmonic impedance of the aggregated distribution network

ICHQP conference, Belo Horizonte, Brazil, 16-19 October 2016
V. Ćuk, F. Ni, W. Jin, A. Jongepier, H.E. van den Brom, G. Rietveld, M. Ačanski, and J.F.G. Cobben.

Abstract
This paper presents a method for measurement of the harmonic impedance of an aggregated distribution network using multiple Phasor Measurement Units (PMUs) with the additional capability of synchronized voltage and current spectrum measurement. The perturbations of the harmonic voltages which originate from the higher voltage levels are distinguished based on the measurements from multiple busbars, and used as the input for the calculation. Results of a test case using measurements from a 50 kV network are given to illustrate the method.